Text |
| 2013-08-23 18:19:05 | RESIDENTIAL (R3) ADDITION, SECOND CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1- REVISE ENERGY CALCULATIONS TO MATCH PLANS: |
| | A) AREA WEIGHTED AVERAGE OVERHANG DEPTH ON ITEM #7 IS |
| | NOT 2.00FT. |
| | B) SPECIFY THE SEER FOR THE PTAC UNIT. |
| | C) SPECIFY THE HEATING ON ITEM #13. |
| | D)REVISE ROOF. MATERIAL IS NOT SHINGLES AND ROOF AREA |
| | IS INCORRECT. |
| | E)REVISE ORIENTATION FOR WALLS, DOORS AND WINDOWS. SEE |
| | VICINITY PLAN FOR CORRECT ORIENTATION. |
| | |
| | 2- REVISE NORTH ARROW SHOWN ON THE SITE PLAN. SEE |
| | VICINITY MAP ON SAME SHEET FOR CORRECT ORIENTATION. |
| | ENERGY CALCULATIONS WERE WRONG BECAUSE OF THIS. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS, DETAILS AND SECTIONS. |
| | B) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | 4- SHEET S-2. REVISE THE DESIGN WIND PRESSURES CHART: |
| | A) REVISE WINDOW/DOOR DESIGN PRESSURES TO CORRESPOND TO |
| | EXPOSURE "C". |
| | B) REVISE SLOPED ROOF DESIGN PRESSURES FOR ROOF ZONE 3 |
| | TO CORRESPOND TO EXPOSURE "C". |
| | C) REVISE THE DIMENSIONS FOR ROOF ZONES 2 AND 3 FOR |
| | PITCHED AND FLAT ROOF. NEED 4'-0" MIN. SEE NOTE "A" ON |
| | FIGURE R301.2(7). |
| | |
| | 5- REVISE NAILING ZONE SPECIFICATIONS ON SHEET S-2: |
| | A) NEED TO SPECIFY 8D RING SHANK NAILS. SEC. |
| | R803.2.3.1. |
| | B) SEE FIGURE R803.2.3.1 FOR DIMENSION OF ROOF ZONE #3. |
| | GABLE END IS THE ROOF ZONE 3 AND THE MINIMUM DIMENSION |
| | IS 5'-0". |
| | |
| | 6- TYP. ADDITION SECTION ON SHEET S-2: |
| | A) REVISE THE LOCATION OF THE CEILING INSULATION. IT |
| | CAN'T BE BLOCKING THE SOFFIT VENT. SEC. R806.3. |
| | |
| | B) A MINIMUM OF 1" SPACE SHALL BE PROVIDED BETWEEN THE |
| | INSULATION AND THE ROOF SHEATHING AND AT THE LOCATION |
| | OF THE VENT. THE 1 X 2 FURRING SHOWN ON THE TYPICAL |
| | WALL SECTION DOESN'T COMPLY WITH SEC. R806.3. REVISE AS |
| | REQUIRED. |
| | |
| | 7- FLAT ROOF FRAMING PLAN: |
| | A) SPECIFY 8D RING SHANK NAILS. SEC. R803.2.3.1. |
| | |
| | B) CROSS VENTILATION IS BLOCKED BY THE 2X10 BLOCKING |
| | SHOWN ON ROOF FRAMING PLAN AND BY THE (3)2X10 BEAM. |
| | SEC. R806.1. |
| | |
| | 8- NEW RIDGE VENT DETAIL SHOWN ON SHEET S-2: |
| | A) PROVIDE PRODUCT APPROVAL FOR THE RIDGE VENT AS |
| | REQUIRED BY DCA RULE 9N-3. AND, ARCHITECT TO REVIEW AND |
| | APPROVE IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | B) DETAIL CALLS FOR "TILE ROOF". PRODUCT APPROVAL |
| | SUBMITTED IS FOR METAL ROOF. REVISE AS REQUIRED TO |
| | MATCH. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH ITEM |
| | TO EXPEDITE THE REVIEW PROCESS. |
| | |