2013-08-06 10:50:03RESIDENTIAL (R3) ADDITION/RENOVATION, PLUMBING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- WATER HEATER LOCATION DOESN'T COMPLY WITH SEC.
 P2801.3 OF 2010 FBC-RESIDENTIAL. NO ENOUGH ROOM FOR
 SERVICING. SEE ALSO SEC. M1305.
  
 2- UPDATE PLUMBING NOTE #9. REFERENCE CURRENT CODE NOT
 2004. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  