| 2013-07-16 17:49:44 | 310 NORTH OLIVE AVENUE | | | PERMIT #13070426 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE A MANUAL PULL STATION NEAR THE MAIN ENTRANCE | | | SETS OF DOUBLE DOORS. | | | | | | THE MANUAL PULL STATION SYMBOL IN THE LEGEND IS | | | DIFFERENT FROM THE SYMBOL USED ON THE PLANS. | | | | | | PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL | | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | (561) 805-6730 | | | [email protected] | | | |
|