| Plan Review Notes For Permit 13070388 |
| Permit Number |
13070388 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-05 15:14:45 | PROVIDE ARC FLASH WARNING LABELS PER 110.16 | | | TIMERS TO HAVE BACKUP PROTECTION PER FBC-EC 505.2.4 | | | VOLTAGE DROP CALCULATIONS TO MEET THE REQUIRMENTS OF | | | FBC-EC 505.7.3 | | | WHAT PROVIDES THE ACTIVATION OF BL1 IN THE MANAGERS | | | OFFIE? IT APPEARS TO BE ACTIVATED ALL THE TIME | | | LIGHTING SCENES, SEQUENCING AND CONTROLS TO MEET THE | | | REQUIREMENTS OF FBC-EC 505.2 | | | PROVIDE LIGHTING POWER DENSITY COMPLIANCE CERTICATION | | | ON ELECTRICAL PLANS PER FBC-EC 505.503 | | | ALL CABLES IN SLAB AND UNDERGROUND TO BE LISTED FOR WET | | | LOCATIONS, INCLUDING POS, DATA, PHONE, AUDIO, ETC. | | | SEPARATE PERMITS WILL BE REQUIRED FOR LOW VOLTAGE, | | | BURGLAR, AUDIO, POS, EAS, AUDIO, ETC. | | | | | | |
|