| Plan Review Notes For Permit 13070370 |
| Permit Number |
13070370 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-05 13:51:05 | 2010 FBC | | | DENIED BY MECHANICAL | | | | | | 1) PROVIDE 2 SETS OF MECHANICAL PLANS SHOWING THE | | | LOCATION AND SIZE OF THE DUCTS, GRILLS AND THE CFMS OF | | | THE SUPPLY AIR FOR THE BEDROOM. FBCR M1601.1 AND CITY | | | AMENDMENTS 107.3.5.3 | | | | | | 2) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED | | | RETURN AIR AT THE NEW BEDROOM. | | | | | | 3) PROVIDE THE SIGNATURE, NAME AND LICENSE NUMBER OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN ON THE MECHANICAL | | | PLANS. CITY AMENDMENTS 107.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|