Plan Review Notes
Plan Review Notes For Permit 13070306
Permit Number 13070306
Review Stop B
Sequence Number 1
Notes
Date Text
2013-07-16 10:25:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE FLOOR PLAN TO INCLUDE ROOM DESIGNATIONS FOR
 ALL OPENINGS.
  
 2. IF THE PROPOSED NEW BEDROOM WINDOWS DO NOT COMPLY
 WITH EMERGENCY ESCAPE AND RESCUE OPENING DIMENSIONS,
 ALSO PROVIDE THE FOLLOWING INFORMATION (FOR BEDROOMS
 ONLY); FBC R310, FBC EB 604.1. THE CLEAR OPENING CANNOT
 BE REDUCED BY MORE THAN 5%:
  
 REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW
 IN THE BEDROOMS - AWNING, CASEMENT, SINGLE HUNG?
  
 REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING
 DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH
 EXISTS WHEN THE WINDOW IS FULLY OPEN.
  
 REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING
 DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE
 MANUFACTURER.
  
  