| Date |
Text |
| 2013-08-01 15:56:23 | 8100 IBIS BOULEVARD |
| | PERMIT #13070299 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ALL BUILDINGS SHALL BE PROPERLY IDENTIFIED EITHER BY |
| | NAME ("FITNESS BLD", "SPA BLD" ETC.) OR NUMERICAL |
| | ADDRESS. PROVIDE BUILDING ADDRESS VISIBLE FROM THE |
| | STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING AND |
| | BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND |
| | SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION |
| | 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA |
| | 1). |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | SHEET EP101B: INSUFFICIENT NUMBER OF NOTIFICATION |
| | APPLIANCES SHOWN IN DINING AREA AND NO DEVICES SHOWN IN |
| | KITCHEN AREA. NO PULL STATION PROVIDED NEAR SECONDARY |
| | EXIT (DOUBLE DOORS). |
| | |
| | SHEET ES101: MONITOR FIRE SPRINKLER BACKFLOW PREVENTER |
| | WITH FIRE ALARM TAMPER SWITCHES. |
| | |
| | SHEET F203: THE SAME FIRE ALARM SYSTEM APPEARS TO |
| | PROTECT BOTH THE FITNESS AREA AND THE BISTRO AREA. IF |
| | THESE AREAS ARE TRULY CONSIDERED THE SAME BUILDING THEN |
| | PROVIDE SPEAKER/STROBE NOTIFICATION APPLIANCES AS NEW |
| | ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING |
| | 300 OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY |
| | VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS. REFERENCE |
| | SECTION 12.3.4.3.3 OF FLORIDA FIRE PREVENTION CODE - |
| | NFPA 101. |
| | |
| | PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE |
| | NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN |
| | THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE |
| | BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR. |
| | |
| | SHEET F203: NO FIRE ALARM NOTIFICATION APPLIANCE IN |
| | SPIN CLASS #203. |
| | |
| | SHEET EP101P: COULD NOT LOCATE ANY MANUAL PULL |
| | STATIONS. |
| | |
| | SHEET EP101S: COULD NOT LOCATE THE FIRE ALARM CONTROL |
| | PANEL FOR THE SPA BUILDING. |
| | |
| | SHEET FP001: COULD NOT REVIEW THIS PLAN BECAUSE ALL THE |
| | TEXT WAS ILLEGIBLE (LETTERS IN THE SAME WORD ARE |
| | DIFFERENT SIZES THROUGHOUT). |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | (561) 805-6730 |
| | [email protected] |
| | |