| 2013-07-30 16:17:01 | BUILDING PLAN REVIEW |
| | PERMIT: 13070299 |
| | ADD: 8100 IBIS BLVD |
| | CONT: THE WEITZ CO. |
| | TEL: (561)686-5511 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: 7/30/2013 |
| | ACTION: DENIED |
| | |
| | 1) THE PHASE 1 SPORTS VILLAGE AT IBIS GOLF & COUNTRY |
| | CLUB IS BEING REVIEWED UNDER A MASTER PERMIT. ONCE THE |
| | MASTER PLAN IS READY TO ISSUE, PERMIT APPLICATIONS FOR |
| | EACH BUILDING AND THE POOL DECK WILL BE REQUIRED FOR |
| | RECORD KEEPING, AND INSPECTIONS TRACKING FOR EACH |
| | STRUCTURE. |
| | |
| | 2) SOILS REPORT. MISSING SOILS REPORT BY ECS FLORIDA, |
| | LLC #25-2169. 2010 FBC-B 1803.6 REPORTING. WHERE |
| | GEOTECHNICAL INVESTIGATIONS ARE REQUIRED, A WRITTEN |
| | REPORT OF THE INVESTIGATIONS SHALL BE SUBMITTED TO THE |
| | BUILDING OFFICIAL BY THE OWNER OR AUTHORIZED AGENT AT |
| | THE TIME OF PERMIT APPLICATION. |
| | |
| | 3) SHEET AE 401 ADA SHOWER ROOM # F117G MEASURES 3'X3'. |
| | THE 2010 FL ACCESSIBILITY CODE SECTION 608.2 DEALS WITH |
| | SIZES AND CLEARANCES THAT WILL COMPLY WITH 608.2. |
| | PLEASE REVIEW 608.2.1 3'X3' TRANSFER TYPE SHOWER |
| | COMPARTMENTS. NO SEAT IS INDICATED, PLEASE PROVIDE |
| | COMPLIANCE WITH 608.4 SEATS. |
| | 608.4 SEATS. A FOLDING OR NON-FOLDING SEAT SHALL BE |
| | PROVIDED IN TRANSFER TYPE SHOWER COMPARTMENTS. A |
| | FOLDING SEAT SHALL BE PROVIDED IN ROLL-IN TYPE SHOWERS |
| | REQUIRED IN TRANSIENT LODGING GUEST ROOMS WITH MOBILITY |
| | FEATURES COMPLYING WITH 806.2. SEATS SHALL COMPLY WITH |
| | 610. |
| | |
| | 4) SHEET AE 401 ADA SHOWER ROOM F124J MEASURES 3'X3.5'. |
| | THE 2010 FL ACCESSIBILITY CODE SECTION 608.2 DEALS WITH |
| | SIZES AND CLEARANCES THAT WILL COMPLY WITH 608.2. |
| | PLEASE REVIEW 608.2.1 3'X3' TRANSFER TYPE SHOWER |
| | COMPARTMENTS. NO SEAT IS INDICATED, PLEASE PROVIDE |
| | COMPLIANCE WITH 608.4 SEATS. |
| | 608.4 SEATS. A FOLDING OR NON-FOLDING SEAT SHALL BE |
| | PROVIDED IN TRANSFER TYPE SHOWER COMPARTMENTS. A |
| | FOLDING SEAT SHALL BE PROVIDED IN ROLL-IN TYPE SHOWERS |
| | REQUIRED IN TRANSIENT LODGING GUEST ROOMS WITH MOBILITY |
| | FEATURES COMPLYING WITH 806.2. SEATS SHALL COMPLY WITH |
| | 610. |
| | |
| | 5) SHEET AE101F THE FIRST FLOOR FITNESS CENTER, THE |
| | LOBBY ROOM F101 INDICATES THAT IT IS OPEN TO ABOVE, |
| | SHEET AE102F INDICATES THE AREA ABOVE THE LOBBY IS OPEN |
| | TO ABOVE, ADJACENT TO THE SPIN CLASS F203. PLEASE |
| | CLARIFY IF THIS AREA COMMUNICATES WITH THE SECOND FLOOR |
| | OR NOT? IT APPEARS THERE MAY BE A HANDRAIL OR |
| | A GLASS ENCLOSURE THAT SEPERATES THIS AREA FROM THE 2ND |
| | FLOOR. PLEASE REVIEW 2010 FBC-B 404.6 ENCLOSURES AT |
| | ATRIUMS. |
| | |
| | 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 7) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 8) SHEETS SR004 & SR005 BOTH APPEAR THE NEGATIVE |
| | PRESSURES APPEAR TO BE A LITTLE LOW, PLEASE PROVIDE |
| | WHAT THE MEAN ROOF HEIGHT IS FOR EACH BUILDING AND THE |
| | MULTIPLIER FOR THE HEIGHT, 2010 FBC-B 1609.7(2). |
| | NEGATIVE PRESSURES ARE TAKEN FROM TOP OF THE BUILDING, |
| | THE MEAN ROOF HEIGTH, MEAN ROOF HEIGHT. THE AVERAGE OF |
| | THE ROOF EAVE HEIGHT AND THE HEIGHT TO THE HIGHEST |
| | POINT ON THE ROOF SURFACE, EXCEPT THAT EAVE HEIGHT |
| | SHALL BE USED FOR ROOF ANGLE OF LESS THAN OR EQUAL TO |
| | 10 DEGREES. |
| | |
| | 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |