| Plan Review Notes For Permit 13070247 |
| Permit Number |
13070247 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-07-09 14:36:43 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE | | | CERTAINTEED MODIFIED ROOFING (NOA NO. 08-0410.09) | | | EXPIRED ON 6/19/13. SUBMIT TWO COPIES OF A CURRENT | | | PRODUCT APPROVAL FOR THE FLAT ROOF. DCA RULE 9N-3 | | | | | | 2) THE SIGNED AND SEALED RAS 117 CALCULATIONS WILL NEED | | | TO BE REDONE BASED ON THE NEW PRODUCT APPROVAL. THEY | | | ARE DATED 6/26/13, SEVEN DAYS AFTER THE EXPIRATION DATE | | | OF THE NOA. CITY AMENDMENTS 107.2.1.3 AND LIMITATION #7 | | | OF THE NOA. | | | | | | 3) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE | | | CERTAINTEED TILE UNDERLAYMENT (NOA NO.10-0119.01) HAS | | | BEEN SUPERSEDED BY NOA NO.11-1129.01. SUBMIT TWO COPIES | | | OF A CURRENT PRODUCT APPROVAL FOR THE TILE | | | UNDERLAYMENT. DCA RULE 9N-3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|