| Plan Review Notes For Permit 13070239 |
| Permit Number |
13070239 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-08-15 10:20:18 | BUILDING PROVISO: | | | FLOOR/ CEILING ASSMBLIES WITH THROUGH PENETRATIONS WILL | | | REQUIRE FIRE STOP SYSTEMS: | | | 2010 FBC-B 713.4.1.1.2 THROUGH-PENETRATION FIRESTOP | | | SYSTEM. | | | THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED | | | THROUGH-PENETRATION | | | FIRESTOP SYSTEM INSTALLED AND TESTED IN ACCORDANCE WITH | | | ASTM E 814 OR UL 1479, | | | WITH A MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 | | | INCH OF WATER (2.49 PA). | | | THE SYSTEM SHALL HAVE AN F RATING/T RATING OF NOT LESS | | | THAN 1 HOUR BUT NOT LESS | | | THAN THE REQUIRED RATING OF THE FLOOR PENETRATED. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|