| 2013-07-27 11:04:42 | 6801 NORTH JOG ROAD - #7 CONSTRUCTION TRAILER |
| | PERMIT #13070205 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | STAIRS SHALL BE A MINIMUM OF 36 INCHES IN WIDTH. STAIR |
| | RISERS SHALL BE BETWEEN 4 INCHES AND 7 INCHES IN |
| | HEIGHT. STAIRS SHALL BE SLIP RESISTANT AND HAVE A |
| | MINIMUM TREAD DEPTH OF 11 INCHES AND PREVENT THE |
| | ACCUMULATION OF WATER. GUARDS, AT LEAST 42-INCHES TALL, |
| | SHALL BE PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS |
| | (STAIRS, MEZZANINE, ETC.) THAT EXCEED 30-INCHES ABOVE |
| | THE FLOOR. OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A |
| | 4-INCH DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE |
| | TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND |
| | BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE |
| | PASSAGE OF A 6-INCH DIAMETER SPHERE. HANDRAILS ARE |
| | REQUIRED ON BOTH SIDES OF THE STAIR. HANDRAILS SHALL BE |
| | LOCATED NOT LESS THAN 34 INCHES AND NOT MORE THAN 38 |
| | INCHES ABOVE THE SURFACE OF THE TREAD, MEASURED |
| | VERTICALLY TO THE TOP OF THE RAIL FROM THE LEADING EDGE |
| | OF THE TREAD. HANDRAIL ENDS SHALL BE RETURNED TO THE |
| | WALL OR FLOOR OR SHALL TERMINATE AT NEWEL POSTS. |
| | HANDRAIL CROSS SECTION SHALL HAVE A DIAMETER OF NOT |
| | LESS THAN 1.25 INCHES AND NOT MORE THAN 2 INCHES. |
| | |
| | PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING |
| | ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE |
| | ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN |
| | HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE |
| | BACKGROUND. |
| | |