| 2013-11-25 18:46:38 | RESIDENTIAL (R3) GARAGE CONVERSION, FOURTH BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1- ENGINEER TO USE CURRENT SEAL AS REQUIRED BY CHAPTER |
| | 471 FLORIDA STATUTE. SEAL THAT SAYS "CERTIFICATE" |
| | INSTEAD OF "LICENSE" IS NOT ALLOWED SINCE 2006. (REPEAT |
| | COMMENT. THREE TIMES). |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) SINGLE HUNG WINDOWS THAT MEET THE DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER OF RECORD. DRAWINGS FOR |
| | FLORIDA PRODUCT APPROVAL FL 11120-R8 SUBMITTED DOESN'T |
| | MEET THE DESIGN PRESSURES SHOWN ON PLANS. |
| | |
| | ***NOTE: ENGINEER OF RECORD APPROVED THIS PRODUCT |
| | APPROVAL, BUT IT DOESN'T MEET THE DESIGN PRESSURES |
| | CALCULATED BY HIM. |
| | |
| | B) HURRICANE SHUTTERS. PROVIDE TWO CLEAR COPIES. SECOND |
| | COPY SUBMITTED IS NOT CLEAR. DRAWINGS ARE INCOMPLETE. |
| | (NOA 12-0320.26). |
| | |
| | C) FRENCH DOORS. PROVIDE TWO COPIES. SECOND COPY |
| | SUBMITTED IS NOT CLEAR. DRAWING S ARE INCOMPLETE. (NOA |
| | 09-0608.16). |
| | |
| | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL OF THE ABOVE PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. (REPEAT COMMENT). |
| | |
| | 4- REVISE SHUTTER INSTALLATION SCHEDULE. DESIGN |
| | PRESSURES TO MATCH THOSE SPECIFIED BY THE ENGINEER OF |
| | RECORD. AND, CLEARLY SPECIFY MOUNTING CONDITION AT TOP |
| | AND BOTTOM TO VERIFY ANCHOR SPACING REQUIRED. SEC. |
| | 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | 5- ENERGY CALCULATIONS SUBMITTED ARE DONE FOR THE |
| | ENTIRE HOUSE. INFORMATION SUBMITTED ON THE ENERGY |
| | CALCULATIONS WILL NEED TO BE VERIFIED IN THE FIELD. |
| | OTHERWISE, INSPECTIONS WILL BE FAILED. PROVIDE WINDOW |
| | AND DOOR SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC |
| | FACTOR SPECIFIED ON THE ENERGY CALCULATIONS AND |
| | SPECIFICATIONS SHOWING HOW THE EXISTING HOUSE WALLS AND |
| | CEILING WILL MEET THE R-VALUE INSULATION SHOWN ON THE |
| | ENERGY CALCULATIONS.. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | 6- TYPICAL WALL SECTION DETAIL WAS REVISED. THE R VALUE |
| | FOR THE WALL IS ONLY FOR THE R VALUE OF THE INSULATION |
| | INSTALLED. CONCRETE BLOCK SHALL NOT BE INCLUDED. SEC. |
| | 304.1.2 OF 2010 FBC-ENERGY CONSERVATION. REVISE AS |
| | REQUIRED. NOTE: PLANS AND ENERGY CALCULATIONS NEED TO |
| | MATCH. |
| | |
| | 7- PROVIDE MANUFACTURER CUT SHEETS FOR EGRESS WINDOW |
| | SIZE 36" X 50" SHOWN ON BEDROOM TO VERIFY COMPLIANCE |
| | WITH SEC. R310 OF 2010 FBC-RESIDENTIAL. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |