| 2013-11-06 13:22:58 | RESIDENTIAL (R3) GARAGE CONVERSION, THIRD MECHANICAL | | | REVIEW CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1- A)PROVIDE EQUIPMENT SIZING CALCULATIONS SHOWING THE | | | MANUFACTURER AND MODEL NUMBERS (INDOOR AND OUTDOOR) AS | | | REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. | | | ***NOTE: EQUIPMENT TO MATCH EQUIPMENT LISTED ON | | | DRAWINGS SUBMITTED. (REPEAT COMMENT). | | | | | | B) CALCULATIONS FOR REPLACEMENT EQUIPMENT NEED TO BE | | | DONE BY AN A/C CONTRACTOR OR LICENSED FLORIDA ENGINEER | | | AS REQUIRED BY SEC. 101.4.7.1.2 OF 2010 FBC-ENERGY | | | CONSERVATION. (REPEAT COMMENT). | | | | | | 2- PLANS TO SHOW COMPLIANCE WITH THE RETURN AIR AND | | | BALANCED RETURN AIR REQUIREMENTS OF SEC. R1602 OF 2010 | | | FBC-RESIDENTIAL. (REPEAT COMMENT). | | | | | | 3- EQUIPMENT LISTED ON THE A/C PLAN TO MATCH ENERGY | | | CALCULATIONS. CHECK SIZE AND SEER AND REVISE AS | | | REQUIRED TO MATCH. SEC. 103.2.2 OF 2010 FBC-ENERGY | | | CONSERVATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|