| Date |
Text |
| 2013-08-01 10:56:47 | RESIDENTIAL (R3) GARAGE CONVERSION, BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- ENGINEER TO USE CURRENT SEAL AS REQUIRED BY CHAPTER |
| | 471 FLORIDA STATUTE. SEAL THAT SAYS "CERTIFICATE" |
| | INSTEAD OF "LICENSE" IS NOT ALLOWED SINCE 2006. AND, |
| | CLARIFY WHY THERE IS AN EXPIRATION DATE OF 2/28/13 |
| | BELOW THE ENGINEER'S LICENSE NUMBER?. |
| | |
| | 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE |
| | DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT |
| | FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 3- SPECIFY SIZE AND TYPE OF WINDOW ON BEDROOM TO VERIFY |
| | COMPLIANCE WITH EGRESS REQUIREMENTS. SEC. R310 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 4- PROVIDE DETAILS AND SPECIFICATIONS SHOWING HOW |
| | OBTAINING R-15 VALUE IN THE CONCRETE BLOCK WALLS AND |
| | R-30 VALUE IN THE FLAT CEILING AS SHOWN ON THE A/C |
| | EQUIPMENT SIZING CALCULATIONS. AND, COORDINATE THE |
| | EQUIPMENT SIZING CALCULATIONS INFORMATION WITH THE |
| | INFORMATION GIVEN IN THE ENERGY CALCULATIONS. SEC. |
| | 405.4.3 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 5- ENERGY CALCULATIONS SUBMITTED; |
| | |
| | A) COORDINATE THE ENERGY CALCULATIONS WITH THE |
| | EQUIPMENT SIZING CALCULATIONS (SEE A/C COMMENTS) AND |
| | FLOOR PLANS SUBMITTED. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC. |
| | 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | C) REVISE ROOF TYPE. ADDITION IS A FLAT ROOF NOT |
| | SHINGLES. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | D) REVISE THE NAME OF THE BUILDER. SEE PERMIT |
| | APPLICATION. AND COMPLETE ALL THE INFORMATION ON TOP OF |
| | FORM, INCLUDING THE OWNER'S NAME. SEC. 103.2.1.1.2 OF |
| | 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 6- ENGINEER TO SPECIFY THE DESIGN PRESSURES FOR DOORS |
| | AND WINDOWS. ***NOTE; ACCORDING TO SEC. R301.2.1.4.3 OF |
| | 2010 FBC-RESIDENTIAL THIS BUILDING IS LOCATED IN |
| | EXPOSURE "C". |
| | |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) WINDOWS SHOWN ON PLANS. |
| | |
| | B) HURRICANE SHUTTERS IF WINDOWS DON'T HAVE HURRICANE |
| | IMPACT GLAZING AND FOR FRENCH DOORS (FRENCH DOORS NOA |
| | 09-0608.16 SUBMITTED IS FOR NON-IMPACT DOOR). |
| | |
| | 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 9- PROVIDE HURRICANE SHUTTERS COMPLETE INSTALLATION |
| | SCHEDULE (SEE SHUTTERS INSTALLATION SCHEDULE SAMPLE ON |
| | THE CITY OF WEST PALM BEACH WEBSITE). SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 10- PROVIDE MANUFACTURER'S INFORMATION FOR DOORS AND |
| | WINDOWS U-FACTOR AND SHGC FACTOR AS SPECIFIED ON ITEM |
| | #7 OF THE ENERGY CALCULATIONS SUBMITTED. SEC. 103.2.2 |
| | OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 11- DRAWING SUBMITTED SHOW TWO EXISTING COLUMNS IN THE |
| | "GARAGE FLOOR RAISED" PLAN. WHERE ARE THESE COLUMNS ON |
| | THE "GARAGE FLOOR PLAN CONVERSION" PLAN?. WHERE THEY |
| | REMOVED?. IF SO, HOW WAS THE STRUCTURE REINFORCED TO |
| | TRANSFER THE LOADS. SEC. 301.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 12- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUE TO |
| | INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND |
| | PROFIT AND PROFESSIONAL DESIGN FEES. REVISE VALUE AS |
| | REQUIRED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |