| Date |
Text |
| 2013-08-28 17:37:42 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1- REVISE DESIGN OF FOOTINGS. SEE RECOMMENDATIONS ON |
| | SOIL TEST REPORT SUBMITTED. |
| | 2- REVISE ENERGY CALCULATIONS: *A) NEED ENERGY |
| | CALCULATIONS FOR EACH SEPARATE BUILDING. **B)PREPARER |
| | TO CERTIFY FORM. ***C)OWNER/AGENT TO CERTIFY FORM. |
| | ****D)COMPLETE ALL THE INFO. ON TOP OF FORM. |
| | *****E)CLARIFY WHAT'S ITEM #8(B) AND REVISE THE R |
| | VALUE. ****** F)CLARIFY WHAT'S ITEM #8(C) AND SPECIFY R |
| | VALUE. *******G)REVISE DOOR TYPE TO MATCH PRODUCT |
| | APPROVALS. ********H)WINDOWS TINTED OR NOT TINTED TO |
| | MATCH PLANS. |
| | 3- PROVIDE MANUFACTURER SPECS FOR THE ICYNENE |
| | INSULATION. |
| | 4- ARCHITECTURAL PLANS TO SHOW: *A)HOW PROVIDING R-30 |
| | IN CEILING (SEE ICYNENE SPECS). **B)R-7 AND R-30 IN |
| | WALLS. ***C)CEILING FAN SIZES IN ALL ROOMS (SEC. |
| | 405.6.6 OF 2010 FBC-ENERGY) AS REQ'D BY THE ENERGY |
| | CALCULATIONS SUBMITTED. |
| | 5-SHEET S-4: SECTION 03 IS INCOMPLETE: PROVIDE COMPLETE |
| | SECTION FROM FIRST FLOOR THRU TOP. AND, SPECIFY ALL |
| | STRUCTURAL FRAMING MEMBERS SIZES, SPACING, FASTENERS |
| | (TOP AND BOTTOM). |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: *A)ENTRY |
| | DOOR THAT MEETS THE CALCULATED PRESSURES AND IS MISSING |
| | THE DOOR DWGS. **B)FIXED WINDOWS NOA 08-0131.04 |
| | SUBMITTED EXPIRED ON MARCH 27, 2013. ***C)ALL USP |
| | STRUCTURAL CONNECTORS (SEE DETAIL 01/S-3). AND UPDATE |
| | ALL SIMPSON FLORIDA PRODUCT APPROVALS NUMBERS SHOWN ON |
| | PLANS. ****D)ARCHED CASEMENT WINDOWS WITH SIZE AS |
| | SPECIFIED ON THE WINDOW SCHEDULE. *****E)CASEMENT |
| | WINDOWS. NOA 08-1112.08 SUBMITTED WAS SUPERSEDED BY |
| | MIAMI-DADE. ****** F)ROOF TILE ADHESIVE, SEE TILE NOA. |
| | ******* G)SHUTTERS AS SHOWN ON PLANS. AND PROVIDE |
| | COMPLETE INSTALLATION SCHEDULE. *****H)STORAGE STEEL |
| | DOOR. NEED DOOR DWGS. |
| | 7- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ABOVE PRODUCT APPROVALS. |
| | 8- SHEET S-0: COMPONENTS & CLADDING DIAGRAM "A" IS |
| | MISSING ROOF ZONE 3. SEE FIGURE R301.2(7). |
| | |