| 2013-07-08 09:35:40 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC-RESIDENTIAL | | | | | | 1- SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE | | | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES OF SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. | | | | | | 2- IF THE DESIGN PRESSURES OF THE SELECTED ASSEMBLY | | | DON'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. | | | R301.2.1.4.3, THEN SIGNED AND SEALED RAS 117 | | | CALCULATIONS ARE REQUIRED (2 COPIES REQUIRED). SEE | | | GENERAL LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|