| 2013-07-23 17:30:54 | RESIDENTIAL (R3) REVISION, MECHANICAL REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- REVISED M.1 PLAN DOESN'T SHOW TRANSFER DUCT IN THE | | | AIR CONDITIONED PORCH AS REQUIRED BY SEC. M1602.4 OF | | | 2010 FBC-RESIDENTIAL. REVISE AS REQUIRED. ORIGINAL PLAN | | | WAS APPROVED WITH THE TRANSFER DUCT SHOWN IN THIS AREA. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|