2013-07-23 17:30:54RESIDENTIAL (R3) REVISION, MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISED M.1 PLAN DOESN'T SHOW TRANSFER DUCT IN THE
 AIR CONDITIONED PORCH AS REQUIRED BY SEC. M1602.4 OF
 2010 FBC-RESIDENTIAL. REVISE AS REQUIRED. ORIGINAL PLAN
 WAS APPROVED WITH THE TRANSFER DUCT SHOWN IN THIS AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712