| Plan Review Notes For Permit 13070121 |
| Permit Number |
13070121 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-02 15:10:24 | LOCATE SMOKE DETECTORS FOR MOST EFFECTIVE COVERAGE IN | | | THE BEDROOMS AND FOR EARLY DETECTION 110.3 | | | PROVIDE CO DETECTOR PER FBC -R 916.1 | | | PROVIDE INTERSYSTEM BONDING POINT 250.94 | | | PROVIDE FOR BONDING OF INTERIOR METAL GAS PIPE | | | NEW LOAD BEING ADDED (AC), PROVIDE LOAD CALCULATION FOR | | | RECORD TO INDICATE EXISTING SERVICE IS OF SUFFICIENT | | | SIZE | | | ARC FAULT BREAKERS REQUIRED AND TAMPERPROOF RECEPTACLES | | | FOR ANY NEW OR REMODELED ITEMS 210.12, 406.11 | | | |
|