Plan Review Notes
Plan Review Notes For Permit 13070121
Permit Number 13070121
Review Stop E
Sequence Number 1
Notes
Date Text
2013-08-02 15:10:24LOCATE SMOKE DETECTORS FOR MOST EFFECTIVE COVERAGE IN
 THE BEDROOMS AND FOR EARLY DETECTION 110.3
 PROVIDE CO DETECTOR PER FBC -R 916.1
 PROVIDE INTERSYSTEM BONDING POINT 250.94
 PROVIDE FOR BONDING OF INTERIOR METAL GAS PIPE
 NEW LOAD BEING ADDED (AC), PROVIDE LOAD CALCULATION FOR
 RECORD TO INDICATE EXISTING SERVICE IS OF SUFFICIENT
 SIZE
 ARC FAULT BREAKERS REQUIRED AND TAMPERPROOF RECEPTACLES
 FOR ANY NEW OR REMODELED ITEMS 210.12, 406.11
  