| 2013-07-23 15:41:54 | REVISION BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | (1)- BUILDING REVIEW WAS APPROVED BACK IN 12/14/12 WITH |
| | A PROVISO (SEE COPY OF PROVISO BELOW). REVISED PLANS |
| | SUBMITTED DON'T ADDRESS THESE ITEMS. NEED TO ADDRESS |
| | THEM NOW BEFORE ANY WORK IS DONE. SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | "BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1- SHEET 1.2: |
| | A) UTILITY AREA NEW OUTDOOR STEPS: (1) PROVIDE COMPLETE |
| | HANDRAILS DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE |
| | WITH LIVE LOAD ON TABLE R301.5 AND SEC. R311.7.7 OF |
| | 2010 FBC-RESIDENTIAL. ENGINEER PLANS ONLY SAY NEW |
| | HANDRAIL DESIGNED BY OTHERS. NO INFORMATION WAS |
| | PROVIDED FOR REVIEW. |
| | |
| | B) NEW STEPS ON REAR SHOWS TREAD SIZE AS 8". MINIMUM |
| | TREAD SIZE IS 10". SEE SEC. R311.7.4.2 OF 2010 |
| | FBC-RESIDENTIAL AND REVISE AS REQUIRED. |
| | |
| | |
| | ***REVISION COMMENTS: |
| | (2) NEED TO ADD THE VALUE THAT REFLECTS THE ADDITIONAL |
| | WORK SHOWN ON PLANS. REVISED PLANS SHOW NEW FLOOR |
| | FRAMING AND NEW ROOF FRAMING. SEC. 109.3 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | (3) PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR THE NEW SIMPSON STRUCTURAL CONNECTORS |
| | SPECIFIED ON REVISED PLANS AND DETAILS. |
| | ***NOTE: PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE |
| | AND PAGE SHOWING THE SPECIFIED CONNECTOR |
| | |
| | ***NOTE: IF DOING ANY ROOFING WORK, THEN SEPARATE |
| | ROOFING PERMIT IS REQUIRED. ROOFING CONTRACTOR IS |
| | REQUIRED AND PROVIDE COMPLETE INFORMATION FOR SUCH |
| | PERMIT. |
| | |