| Plan Review Notes For Permit 13070068 |
| Permit Number |
13070068 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-07-05 11:24:22 | 1475 CENTERPARK BOULEVARD - SUITE #140 | | | PERMIT #13070068 | | | MASTER #13060068 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | NO SUITE NUMBER PROVIDED IN PLAN TITLEBLOCK. | | | | | | BREAK ROOM #110 MAY HAVE AN ACCORDIAN DOOR THAT | | | SEPARATES THE ROOM INTO TWO ROOMS WHEREBY AN ADDITIONAL | | | NOTIFICATION WOULD BE NEEDED. | | | | | | SEVERAL NOTIFICATION APPLIANCES APPEAR TO BE LOCATED | | | TOO FAR FROM ADJACENT WALLS INCLUDING ADMIN #103, | | | WORKROOM #107, AND CORRIDOR #109. | | | | | | INSUFFICIENT NOTIFICATION APPLIANCES PROVIDED AT | | | SOUTHWEST AREA OF LARGE OPEN OFFICE #105. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|