| Plan Review Notes For Permit 13070068 |
| Permit Number |
13070068 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-07-05 12:41:24 | 13070068 | | | 1427 CENTREPARK BLVD. #140 | | | FIRE ALARM SYSTEM | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE CONDUCTOR TYPE AND SIZE. FBC 907.1.2 | | | VERIFY WIRING METHODS AND WALL PENETRATIONS ARE | | | PROTECTED AND APPROPRIATELY FIRE RATED. NEC 300.21 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | | | | |
|