| Plan Review Notes For Permit 13070017 |
| Permit Number |
13070017 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-07-05 07:20:51 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. THIS PARCEL IS LOCATED IN EXPOSURE C, 170MPH (VULT) | | | FBC 2010 RESIDENTIAL 301. REVISE PLANS AND TRUSS | | | ENGINEERING. | | | | | | 2. CARBON MONOXIDE DETECTORS REQUIRED, FBC 2010 | | | RESIDENTIAL 315. | | | | | | 3. THIS PERMIT WAS ISSUED WITH PROVISO THAT SHUTTERS | | | FOR THE NON IMPACT FIXED WINDOW WOULD REQUIRE A | | | SEPARATE PERMIT. PLEASE APPLY. | | | | | | 4. THIS PERMIT WAS ISSUED WITH PROVISO THAT AN ORIGINAL | | | SOILS INVESTIGATION REPORT BE SUBMITTED. THE SOILS | | | DENSITY REPORT REFERS TO AN INVESTIGATION REPORT DATED | | | JULY 15, 2003. PLEASE SUBMIT. | | | | | | 5. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, | | | FAC9N-3. PROVIDE CURRENT APPROVALS FOR COMPONENTS AND | | | CLADDING INSTALLED. IF UNAVAILABLE, PLEASE CONTACT ME. | | | |
|