| Plan Review Notes For Permit 13061115 |
| Permit Number |
13061115 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-07-08 12:50:18 | 13061115 | | | 3080 ARLINGTON ROAD | | | SFD REMODEL | | | | | | THE SCOPE OF THE PROPOSED ELECTRICAL WORK IS NOT CLEAR. | | | PROVIDE A DETAILED ELECTRICAL PLAN FOR ALL | | | IMPROVEMENTS. | | | | | | INDICATE THE SIZE, RATING, LOCATION OF THE EXISTING | | | SERVICE, MAIN DISCONNECT AND PANEL BOARD. SHOW SERVICE | | | AND PANEL BOARD LOCATIONS. SHOW NEW AND EXISTING | | | OUTLETS. INCLUDE A PANEL SCHEDULE. NEC 215.5 | | | | | | ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI PROTECTED. | | | NEC 210.12 | | | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE | | | RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A | | | FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED | | | WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC | | | R313 | | | | | | SHOW THE KITCHEN COUNTER TOP RECEPTACLES TO BE GFCI | | | PROTECTED. NEC 210.8 | | | | | | GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND | | | REAR ELEVATIONS. NEC 210.8 | | | | | | PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE BRANCH | | | CIRCUITS. NEC 210.52 | | | | | | PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS. | | | NEC 210.11 (C)(3) | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | | | | |
|