| Plan Review Notes For Permit 13061104 |
| Permit Number |
13061104 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-08-17 19:07:41 | 5800 SOUTH DIXIE HIGHWAY | | | PERMIT #13061104 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PER NFPA 101, SECTION 8.3.2.4, EACH FIRE BARRIER SHALL | | | BE PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING | | | READING FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS | | | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN | | | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 | | | FEET ON CENTER. | | | | | | PER NFPA 101, SECTION 8.3.5.1, PENETRATIONS THROUGH A | | | FIRE-RATED WALL ASSEMBLY SHALL BE PROTECTED BY A | | | FIRESTOP SYSTEM OR DEVICE. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|