| Plan Review Notes For Permit 13061104 |
| Permit Number |
13061104 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-12-09 17:08:33 | ELECTRICAL REVIEW DENIED FOR THE SECOND TIME. AS | | | PREVIOUSLY STATED ON THE FIRST REVIEW, IF A BATHROOM IS | | | REQUIRED, YOU SHALL INCLUDE ON THE DRAWINGS THE MINIMUM | | | ELECTRICAL REQUIREMENTS FOR THE BATHROOMS. AS PART OF | | | THE ELECTRICAL SUBMITTAL, A PANEL SCHEDULE SCHEDULE | | | REFLECTING THE BATHROOM CKT. AS WELL AS THE EMERGENCY | | | LIGHTING SHALL BE PROVIDED. | | | |
|