Plan Review Notes
Plan Review Notes For Permit 13061001
Permit Number 13061001
Review Stop B
Sequence Number 2
Notes
Date Text
2013-08-31 14:29:26***COURTESY REVIEWS WERE PERFORMED VIA EMAIL**
  
 EMAIL FROM 8/31:
  
 BEFORE I DO ANOTHER COURTESY REVIEW, PLEASE REFER TO MY
 COMMENT LIST, AND THEN CIRCLE OR HIGHLIGHT ON THE TEST
 YOU WISH FOR ME TO REVIEW THE TEST STANDARD USED. THERE
 SHOULD BE A TOTAL OF 3 (IIC, STC, FLAME SPREAD).
  
 IF YOU CANNOT FIND THE TEST CIRCLED REFERENCED IN THE
 COMMENT LIST, THEY'D NEED TO SUBMIT A REQUEST FOR
 ALTERNATIVE MATERIALS AND METHODS TO PROVIDE DATA TO
 JUSTIFY WHY THEY ELECTED TO USE A DIFFERENT TEST, OR A
 DIFFERENT METHOD, OR PROVIDE DATA/ENGINEERING TO SHOW
 WHY THEY DO NOT NEED TO PERFORM THE TEST PRESCRIBED BY
 THE FBC AND IBC (THEREFORE A NATIONAL REQUIREMENT
 ANYWHERE THAT USES THE ICC AS BASE CODE). ALSO CHECK
 THAT NONE OF THE TESTS INCLUDE A SUSPENDED DRYWALL
 CEILING.
  
 I STARTED TO LOOK AT THE DOCUMENTS - THE FIRST HAD A
 SUSPENDED CEILING. THE SECOND DID NOT MEET THE
 REQUIREMENTS OF THE STANDARDS OF THE TEST. PLEASE TAKE
 THE TIME TO READ THE TEST REPORTS BEFORE SENDING. BY
 NOW YOU SHOULD BE AN EXPERT!
  
 AFTER YOU CONFIRM THAT, TO THE BEST OF YOUR KNOWLEDGE,
 THE PRODUCT MEETS THE REQUIREMENTS OF THE FBC, PLEASE
 FEEL FREE TO SEND TO ME.