| 2013-06-26 14:06:56 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY FROM NOA | | | 12-0815.07 SUBMITTED IS GOING TO BE INSTALLED TO VERIFY | | | COMPLIANCE WITH SEC. R301.2.1.4.3 OF 2010 | | | FBC-RESIDENTIAL. | | | | | | 2- IF DESIGN PRESSURES FROM SELECTED ASSEMBLY DON'T | | | MEET THE DESIGN PRESSURES FOR THE PERIMETER AND CORNER | | | AREAS, THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE | | | REQUIRED. SEE GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. DESIGN PRESSURES ARE CALCULATED BASED ON | | | SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|