| Plan Review Notes For Permit 13060970 |
| Permit Number |
13060970 |
|
| Review Stop |
B |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2014-03-11 17:06:27 | ****CORRECTIONS**** | | | 2/26 SUBMITTAL | | | | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FROM PREVIOUS LIST: | | | | | | 2. ENGINEER SPECIFIES -100PSF ROOF PRESSURES ZONE 2. | | | PRODUCT APPROVAL SUBMITTED HAS A LIMITATION OF -80.9. | | | PLEASE ADDRESS. | | | | | | 3/11/14 - ENGINEER RESPONSE IS THAT THE UPLIFT | | | (ULTIMATE) ON THE PLAN IS 100PSF, WHICH CONVERTS TO | | | 60PSF. PROVIDE CALCULATIONS/EXPLANATION. THE NOA | | | SPECIFIES FASTENING 3" APART IN THE 3" RIBS. SEE FBC | | | 2010 RESIDENTIAL TABLES 301.2(2) AND (3). ZONE 3, 10SF | | | OR LESS, EXPOSURE C, IS -131.8PSF ULTIMATE AND -95.7 | | | ASD. IT IS NOT CLEAR HOW ENGINEER HAS ARRIVED AT A | | | PRESSURE OF -60PSF ASD, -135 ULTIMATE. | | | | | | | | 2014-02-27 10:10:56 | SENT S HILL |
|