| Plan Review Notes For Permit 13060970 |
| Permit Number |
13060970 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2014-02-03 18:38:03 | ****CORRECTIONS**** | | | SUBMITTALS 1/21 AND 1/24 WERE THE SAME | | | | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FROM PREVIOUS LIST: | | | | | | 1. ENGINEER OF RECORD IS TO REVIEW PRODUCT APPROVAL, | | | FBC 107, FBC 2010 RESIDENTIAL 301. | | | | | | 2ND REVIEW - | | | | | | ENGINEER OF RECORD IS TO REVIEW PRODUCT APPROVAL, FBC | | | 107, FBC 2010 RESIDENTIAL 301. HAVE THIS DONE PRIOR TO | | | SUBMITTAL. | | | | | | NEW COMMENT: | | | | | | 2. ENGINEER SPECIFIES -100PSF ROOF PRESSURES ZONE 2. | | | PRODUCT APPROVAL SUBMITTED HAS A LIMITATION OF -80.9. | | | PLEASE ADDRESS. |
|