| Plan Review Notes For Permit 13060970 |
| Permit Number |
13060970 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-08-19 11:17:56 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. THE PRODUCT APPROVAL FOR THE ROOF PANELS DOES NOT | | | INCLUDE A FASTENING DETAIL OR INFORMATION REGARDING | | | RESISTANCE TO WIND LOADS. EITHER REVISE THE PLAN TO | | | INCLUDE THIS INFORMATION OR PROVIDE FASTENING | | | SPECIFICATION. ENGINEER OF RECORD IS TO REVIEW PRODUCT | | | APPROVAL, FBC 107, FBC 2010 RESIDENTIAL 301. | | | |
|