| 2013-06-26 09:58:03 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | INDICATE WIRING METHOD. PROVIDE SPECIFICATIONS AND | | | LISTING FOR EQUIPMENT. PROVIDE LAYOUT OR DESCRIPTION OF | | | THE PROPOSED LOCATION OF WIRING FROM SOURCE TO | | | DESTINATION. PROVIDE A TYPICAL FIRE STOP DETAIL FOR ALL | | | PENETRATIONS OF RATED ASSEMBLIES. CABLES AND CONDUIT | | | MAY NOT BE LOCATED WITHIN SHAFTS, OR WITHIN EGRESS | | | STAIR WAYS. WIRING LOCATED IN DAMP OR WET LOCATIONS | | | MUST BE LISTED FOR THE LOCATION. NEC 110.3, 110.12 | | | 110.8, 300.21 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | 561-805-6718 | | | | | | |
|