2013-06-26 09:52:32PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 INDICATE WIRING METHOD. PROVIDE SPECIFICATIONS AND
 LISTING FOR EQUIPMENT. PROVIDE LAYOUT OR DESCRIPTION OF
 THE PROPOSED LOCATION OF WIRING FROM SOURCE TO
 DESTINATION. PROVIDE A TYPICAL FIRE STOP DETAIL FOR ALL
 PENETRATIONS OF RATED ASSEMBLIES. CABLES AND CONDUIT
 MAY NOT BE LOCATED WITHIN SHAFTS, OR WITHIN EGRESS
 STAIR WAYS. WIRING LOCATED IN DAMP OR WET LOCATIONS
 MUST BE LISTED FOR THE LOCATION. NEC 110.3, 110.12
 110.8, 300.21
  
  