| Plan Review Notes For Permit 13060868 |
| Permit Number |
13060868 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2013-11-25 16:49:04 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. OK. | | | | | | 2. FBC 2010 EXISTING BUILDING 912.4.1, FBC 2010 | | | BUILDING 1031.2, PANIC AND FIRE EXIT HARDWARE REQUIRED | | | WHERE THE MEANS OF EGRESS DOOR SERVES AN OCCUPANT LOAD | | | GREATER THAN 100. SEE ALSO COMMENT 3; OCCUPANT LOAD. | | | REVISE PLAN TO SHOW LOCATIONS REQUIRED, IF ANY. | | | | | | 2ND REVIEW, REQUIREMENTS CANNOT BE DETERMINED DUE TO | | | LACK OF INFORMATION, SEE ITEM 3. | | | | | | 3RD REVIEW, PLANS INDICATE THAT ALL DOORS WILL HAVE | | | PANIC DEVICES. PLANS ALSO HAVE A STATEMENT THAT ALL | | | INFORMATION WAS PROVIDED BY OWNER. DESIGNER OF RECORD | | | TO DETERMINE WHETHER EXTERIOR DOORS HAVE PANIC DEVICES | | | AND TO INCLUDE IN SCOPE OF WORK IF THEY ARE NEEDED. AS | | | THEY ARE COMPONENTS AND CLADDING, PRODUCT APPROVALS | | | REQUIRED. | | | | | | 3. OK | | | | | | 4. OK | | | | | | 5. FBC 2010 EXISTING BUILDING 912.5, HEIGHT AND AREA TO | | | COMPLY WITH FBC 2010 BUILDING TABLE 503 FOR BUILDING | | | HEIGHT & AREA. | | | | | | 2ND REVIEW, RESPONSE LETTER STATES THIS IS COMPLETED. | | | IT IS NOT CLEAR HOW THIS WAS ADDRESSED AS NO | | | INFORMATION ABOUT THE EXISTING BUILDING WAS PROVIDED. | | | | | | 3RD REVIEW, PLEASE ADDRESS. | | | | | | 6. OK | | | | | | NEW COMMENT: | | | | | | PLEASE NOTE THAT THIS IS A CHANGE OF OCCUPANCY AS WELL | | | AS A LEVEL 2 ALTERATION. PLEASE INCLUDE THIS | | | INFORMATION ON THE PLAN. | | | | | | | | | |
|