| 2013-08-09 15:27:09 | PERMIT #13060868 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PROVIDE A SCALABLE PLAN. |
| | |
| | STORAGE ROOMS SHALL BE SEPERATED FROM THE OTHER ROOMS |
| | WITH A 1-HOUR RATED FIRE WALL AND 45-MINUTE FIRE RATED |
| | DOOR. |
| | |
| | EXIT ACCESS CORRIDORS SHALL BE AT LEAST 6 FEET IN |
| | WIDTH. |
| | |
| | CORRIDORS SHALL BE SEPERATED FROM OTHER AREAS WITH A |
| | 1-HOUR RATED BARRIER AND A 45-MINUTE DOOR. |
| | |
| | AN ACCURATE AND DETAILED FURNITURE PLAN MUST BE |
| | SUBMITTED. |
| | |
| | CLUSTER OF OFFICES EXCEEDS 10 PERCENT OF THE OVERALL |
| | SPACE USED, CLASSIFYING IT AS A NON-SEPERATED MIXED USE |
| | OCCUPANCY. |
| | THE LARGE CLASSROOM AREA (LABELED "CAFETERIA" IN THE |
| | ORIGINAL PLANS) HAS AN AREA WHICH RESULTS IN AN |
| | OCCUPANT LOAD GREATER THAN 50 PERSONS, CLASSIFYING IT |
| | AS AN ASSEMBLY OCCUPANCY. |
| | FOR NON-SEPARATED MIXED USE OCCUPANCIES, THE MOST |
| | STRINGENT FIRE AND LIFE SAFETY REQUIREMENTS OF EACH |
| | OCCUPANCY SHALL APPLY TO THE BUILDING. |
| | |
| | PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES, |
| | OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY |
| | LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC. |
| | THE LOCATIONS OF THE EXIT SIGNS AND EMERGENCY LIGHTS |
| | MUST BE CLEARLY IDENTIFIED. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | ALL ROOMS SHOULD BE DESIGNATED WITH A NAME OR FUNCTION. |
| | |
| | |