| 2013-08-12 11:40:05 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. FBC 2010 EXISTING BUILDING 912.2.2, FBC 2010 |
| | BUILDING 907.2.3, FIRE ALARM REQUIRED. |
| | |
| | 2ND REVIEW, PLEASE ADVISE WHEN THIS IS ISSUED. |
| | |
| | 2. FBC 2010 EXISTING BUILDING 912.4.1, FBC 2010 |
| | BUILDING 1031.2, PANIC AND FIRE EXIT HARDWARE REQUIRED |
| | WHERE THE MEANS OF EGRESS DOOR SERVES AN OCCUPANT LOAD |
| | GREATER THAN 100. SEE ALSO COMMENT 3; OCCUPANT LOAD. |
| | REVISE PLAN TO SHOW LOCATIONS REQUIRED, IF ANY. |
| | |
| | 2ND REVIEW, REQUIREMENTS CANNOT BE DETERMINED DUE TO |
| | LACK OF INFORMATION, SEE ITEM 3. |
| | |
| | 3. FBC 2010 EXISTING BUILDING 912.4.1, FBC 2010 |
| | BUILDING 1004.1.1, LABEL EACH ROOM WITH OCCUPANCY |
| | CLASSIFICATION AND OCCUPANT LOAD FOR EACH ROOM. |
| | ALTHOUGH THE SCHOOL BOARD HAS DETERMINED THAT YOU CAN |
| | HAVE A MAXIMUM OF 150 STUDENTS, THE FLORIDA BUILDING |
| | CODE REQUIRES EXITING IN COMPLIANCE WITH FBC 2010 TABLE |
| | 1004. |
| | |
| | NOT ADDRESSED. RESPONSE LETTER STATES THAT PLAN WAS |
| | REVISED. PLAN SHOWS RATIOS SUCH AS 1:10, 1:18. THIS IS |
| | NOT AN OCCUPANT LOAD. SEE FBC TABLE 1004. EACH ROOM |
| | SHOULD STATE OCCUPANT LOAD (EITHER DESIGN LOAD OR |
| | OCCUPANT LOAD FROM TABLE 1004, WHICHEVER IS GREATER). |
| | |
| | 4. OK |
| | |
| | 5. FBC 2010 EXISTING BUILDING 912.5, HEIGHT AND AREA TO |
| | COMPLY WITH FBC 2010 BUILDING TABLE 503 FOR BUILDING |
| | HEIGHT & AREA. |
| | |
| | 2ND REVIEW, RESPONSE LETTER STATES THIS IS COMPLETED. |
| | IT IS NOT CLEAR HOW THIS WAS ADDRESSED AS NO |
| | INFORMATION ABOUT THE EXISTING BUILDING WAS PROVIDED. |
| | |
| | 6. IMPACT FEE ASSESSMENT REQUIRED BY PALM BEACH COUNTY. |
| | 561-233-5025 FOR MORE INFORMATION. PROVIDE STAMPED PLAN |
| | AND RECEIPT, IF APPLICABLE. |
| | |
| | 2ND REVIEW, NOT ADDRESSED. THIS MAY BE DONE AT THE END |
| | OF PLAN REVIEW PROCESS BUT MUST BE DONE PRIOR TO |
| | ISSUANCE OF A PERMIT. |
| | |