| 2013-06-27 11:10:33 | 13060868 | | | 901 NORTH POINT PKWY | | | CHANGE OF USE TO EDUCATIONAL | | | | | | VERIFY THAT THE REQUIRED WORKING CLEARANCES AND | | | DEDICATED WORKING SPACE HAS BEEN PROVIDED FOR THE | | | ELECTRICAL EQUIPMENT AND PANEL BOARDS. NEC 110.26, | | | 240.24, 408.17 | | | | | | A FIRE ALARM SYSTEM IS REQUIRED FOR THIS FACILITY. A | | | SEPARATE PERMIT WITH PLAN AND SHOP DRAWINGS IS | | | REQUIRED. NFPA 101 15.3.4, FBC 907.2.3 | | | | | | VERIFY THE MEANS OF EGRESS HAS EMERGENCY ILLUMINATION | | | AND EXIT SIGNS. FBC 1006.2 1011.1 | | | | | | VERIFY COMPLIANCE WITH REQUIRED ILLUMINATION LEVEL, | | | UNIFORMITY, BRIGHTNESS AND GLARE IN | | | CLASSROOMS/INSTRUCTION SPACES. FBC 443.3.7 | | | | | | GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS. | | | NEC 422.52 | | | | | | VENDING MACHINES IF PROVIDED SHALL BE PROTECTED WITH | | | GFCI?S. NEC 422.51 | | | | | | ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS MUST | | | BE GFCI PROTECTED. NEC 210.8 | | | | | | NOTE: | | | SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE, | | | DATA, FIRE ALARM, AND SECURITY. | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | 561-805-6718 | | | | | | | | | |
|