Plan Review Notes
Plan Review Notes For Permit 13060868
Permit Number 13060868
Review Stop B
Sequence Number 1
Notes
Date Text
2013-07-01 12:39:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 2010 EXISTING BUILDING 912.2.2, FBC 2010
 BUILDING 907.2.3, FIRE ALARM REQUIRED.
  
 2. FBC 2010 EXISTING BUILDING 912.4.1, FBC 2010
 BUILDING 1031.2, PANIC AND FIRE EXIT HARDWARE REQUIRED
 WHERE THE MEANS OF EGRESS DOOR SERVES AN OCCUPANT LOAD
 GREATER THAN 100. SEE ALSO COMMENT 3; OCCUPANT LOAD.
 REVISE PLAN TO SHOW LOCATIONS REQUIRED, IF ANY.
  
 3. FBC 2010 EXISTING BUILDING 912.4.1, FBC 2010
 BUILDING 1004.1.1, LABEL EACH ROOM WITH OCCUPANCY
 CLASSIFICATION AND OCCUPANT LOAD FOR EACH ROOM.
 ALTHOUGH THE SCHOOL BOARD HAS DETERMINED THAT YOU CAN
 HAVE A MAXIMUM OF 150 STUDENTS, THE FLORIDA BUILDING
 CODE REQUIRES EXITING IN COMPLIANCE WITH FBC 2010 TABLE
 1004.
  
 4. PLEASE REVISE PLAN TO NOTE WHETHER THIS WILL BE USED
 FOR CLASSROOM/SCHOOL ONLY, OR ALSO FOR DAY CARE FBC
 2010 BUILDING 1037.
  
 5. FBC 2010 EXISTING BUILDING 912.5, HEIGHT AND AREA TO
 COMPLY WITH FBC 2010 BUILDING TABLE 503 FOR BUILDING
 HEIGHT & AREA.
  
 6. IMPACT FEE ASSESSMENT REQUIRED BY PALM BEACH COUNTY.
 561-233-5025 FOR MORE INFORMATION. PROVIDE STAMPED PLAN
 AND RECEIPT, IF APPLICABLE.