| Plan Review Notes For Permit 13060838 |
| Permit Number |
13060838 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-06-24 15:20:29 | FIRE ALARM SYSTEM ADDITIONS | | | TOMMY BAHAMAS | | | 701 SOUTH ROSEMARY AVENUE | | | PERMIT # 13060838 | | | | | | 1. FIRE ALARM INSTALLATIONS TO COMPLY WITH NFPA 72, THE | | | NATIONAL FIRE ALARM CODE. | | | | | | 2. NOTE # 15 IS INCORRECT. DUCT DETECTORS WHEN | | | ACTIVATED SHALL CAUSE A FIRE ALARM SYSTEM ACTIVATION | | | NOT A SUPERVISORY SIGNAL AS PER LOCAL REQUIREMENTS. | | | | | | APPROVED PROVISO | | | | | | | | | MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF | | | WEST PALM BEACH FIRE RESCUE |
|