| 2014-04-11 12:36:33 | BUILDING PLAN REVIEW |
| | PERMIT: 13060815 |
| | ADD: 2823 N AUSTRALIAN AVE |
| | CONT: BLACKBURN BUILDING CO |
| | TEL: (561)775-5653 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: FRIDAY APRIL 11/2014 |
| | ACTION: DENIED |
| | |
| | NOTE SCOPE OF WORK HAS CHANGED, PHASES II & III WERE |
| | ADDED IN THE SCOPE OF THIS PERMIT. |
| | |
| | 1) PLEASE REVIEW SHEETS A1.02 AND THE ROOMS 220 & 221, |
| | BOTH SHOWING THE USE OF ACCORDIAN DOORS. WHEN THE |
| | ACCORDIAN DOOR BETWEEN THE 2 ROOMS IS PULLED BACK |
| | CREATING ONE LARGE ROOM THE OCCUPANT LOAD IS 17 |
| | COMBINED. THE 2010 FBC-B 1008.1.2 DOOR SWING. |
| | EGRESS DOORS SHALL BE OF THE PIVOTED OR SIDE-HINGED |
| | SWINGING TYPE. |
| | EXCEPTIONS: |
| | 1. PRIVATE GARAGES, OFFICE AREAS, FACTORY AND STORAGE |
| | AREAS WITH AN OCCUPANT LOAD OF 10 OR LESS. |
| | |
| | 2) SHEET A1.02 CORRIDOR WALLS ARE DESIGNATED AS A SMOKE |
| | WALL P2, DOES NOT INDICATE THE WALL GOING TO THE TOP OF |
| | THE DECK ABOVE OR TO THE FLOOR INDICATING IT TO BE A |
| | SMOKE PARTITION. 711.4 CONTINUITY. |
| | SMOKE PARTITIONS SHALL EXTEND FROM THE TOP OF THE |
| | FOUNDATION OR FLOOR BELOW TO THE UNDERSIDE OF THE FLOOR |
| | OR ROOF SHEATHING, DECK OR SLAB ABOVE OR TO THE |
| | UNDERSIDE OF THE CEILING ABOVE WHERE THE CEILING |
| | MEMBRANE IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE. |
| | |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |