2014-04-11 12:36:33BUILDING PLAN REVIEW
 PERMIT: 13060815
 ADD: 2823 N AUSTRALIAN AVE
 CONT: BLACKBURN BUILDING CO
 TEL: (561)775-5653
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRIDAY APRIL 11/2014
 ACTION: DENIED
  
 NOTE SCOPE OF WORK HAS CHANGED, PHASES II & III WERE
 ADDED IN THE SCOPE OF THIS PERMIT.
  
 1) PLEASE REVIEW SHEETS A1.02 AND THE ROOMS 220 & 221,
 BOTH SHOWING THE USE OF ACCORDIAN DOORS. WHEN THE
 ACCORDIAN DOOR BETWEEN THE 2 ROOMS IS PULLED BACK
 CREATING ONE LARGE ROOM THE OCCUPANT LOAD IS 17
 COMBINED. THE 2010 FBC-B 1008.1.2 DOOR SWING.
 EGRESS DOORS SHALL BE OF THE PIVOTED OR SIDE-HINGED
 SWINGING TYPE.
 EXCEPTIONS:
 1. PRIVATE GARAGES, OFFICE AREAS, FACTORY AND STORAGE
 AREAS WITH AN OCCUPANT LOAD OF 10 OR LESS.
  
 2) SHEET A1.02 CORRIDOR WALLS ARE DESIGNATED AS A SMOKE
 WALL P2, DOES NOT INDICATE THE WALL GOING TO THE TOP OF
 THE DECK ABOVE OR TO THE FLOOR INDICATING IT TO BE A
 SMOKE PARTITION. 711.4 CONTINUITY.
 SMOKE PARTITIONS SHALL EXTEND FROM THE TOP OF THE
 FOUNDATION OR FLOOR BELOW TO THE UNDERSIDE OF THE FLOOR
 OR ROOF SHEATHING, DECK OR SLAB ABOVE OR TO THE
 UNDERSIDE OF THE CEILING ABOVE WHERE THE CEILING
 MEMBRANE IS CONSTRUCTED TO LIMIT THE TRANSFER OF SMOKE.
  
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  