| Plan Review Notes For Permit 13060815 |
| Permit Number |
13060815 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-09-09 13:35:04 | SUPPLEMENTAL REVIEW - 9-25-13 | | | | | | THIS REVIEW WAS DONE WITH CONSIDERATION THAT THIS IS A | | | BUSINESS FACILTY AS OPPOSED TO AN EDUCATIONAL FACILTY. | | | THE FOLLOWING CORRECTIONS ARE REQUIRED. | | | | | | 1. PLEASE PROVIDE AN ELECRICAL DRAWING SHOWING ALL | | | ELECTRICAL BOTH EXISTING AND NEW. PLEASE INCLUDE | | | CIRCUIT NUMBERS ON THE FLOOR PLAN AS WELL. | | | | | | 2. PLEASE PROVIDE A PANEL SCHEDULE SHOWING ALL REQUIRED | | | INFORMATION PER NEC 408.4 | | | | | | 3. PROVIDE GFCI PROTECTION FOR WATER COOLERS PER NEC | | | 422.52 | | | | | | END REVIEW | | | |
|