2013-07-08 09:56:5213060815
 2823 N. AUSTRALIAN AVE. BLDG. 2
 NEW EDUCATIONAL FACILITY
  
 THE SCOPE OF THE PROPOSED ELECTRICAL WORK IS NOT CLEAR.
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A PLAN SHOWING THE ELECTRICAL SYSTEM. SHOW ALL
 NEW AND EXISTING ELECTRICAL OUTLETS INCLUDING LIGHTING.
  
 VERIFY THAT THE REQUIRED WORKING CLEARANCES AND
 DEDICATED WORKING SPACE HAS BEEN PROVIDED FOR THE
 ELECTRICAL EQUIPMENT AND PANEL BOARDS. NEC 110.26,
 240.24, 408.17
  
 A FUNCTIONING FIRE ALARM SYSTEM IS REQUIRED FOR THIS
 FACILITY. NFPA 101 15.3.4, FBC 907.2.3
  
 VERIFY COMPLIANCE WITH REQUIRED ILLUMINATION LEVEL,
 UNIFORMITY, BRIGHTNESS AND GLARE IN
 CLASSROOMS/INSTRUCTION SPACES. FBC 443.3.7
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLANS SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. 2010 FBC ENERGY CONSERVATION T505.3
  
 GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS.
 NEC 422.52
  
 VENDING MACHINES IF PROVIDED SHALL BE PROTECTED WITH
 GFCI?S. NEC 422.51
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS MUST
 BE GFCI PROTECTED. NEC 210.8
  
 NOTE:
 SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE,
 DATA, FIRE ALARM, AND SECURITY.
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  
  