| 2013-07-05 15:20:57 | BUILDING PLAN REVIEW |
| | PERMIT: 13060815 |
| | ADD: 2823 N AUSTRALIAN AVE |
| | CONT: BLACKBURN BUILDING CO |
| | TEL: (561)775-5653 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: JULY 07/2013 |
| | ACTION: DENIED |
| | |
| | 1) THE COVERSHEET A0.00 UNDER THE HEADING PROJECT |
| | DESCRIPTION INDICATES 2ND FLOOR FROM A FREE CLINIC TO |
| | AFTER SCHOOL TRAINING & DEVELOPMENT FOR MIDDLE AND HIGH |
| | SCHOOL YOUTH. THIS IS A CHANGE OF OCCUPANCY FROM A (B) |
| | BUSINESS OCCUPANCY TO (E) EDUCATIONAL OCCUPANCY. FBC-B |
| | 305.1 EDUCATIONAL GROUP E. EDUCATIONAL GROUP E |
| | OCCUPANCY INCLUDES, AMONG OTHERS, THE USE OF A BUILDING |
| | OR STRUCTURE, OR A PORTION THEREOF, BY SIX OR MORE |
| | PERSONS AT ANY ONE TIME FOR EDUCATIONAL PURPOSES |
| | THROUGH THE 12TH GRADE. |
| | 2010 FBC-B 901.3.1 PARTIAL CHANGE OF OCCUPANCY |
| | CLASSIFICATION. WHERE A PORTION OF AN EXISTING BUILDING |
| | IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION |
| | 912 SHALL APPLY. |
| | |
| | 1A) THE COVER SHEET NEEDS TO UPDATE THE 2010 FBC'S |
| | FAMILY OF CODES, PLUMBING, MECHANICAL & ACCESSIBILITY |
| | TO 2010. ALL ADOPTED IN MARCH 15/ 2012. THE 2012 |
| | SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2) THE DESIGNER OF RECORD WILL NEED TO DECLARE EXST |
| | BLDG 912.1.1 COMPLIANCE WITH CHAPTER 8. THE |
| | REQUIREMENTS OF CHAPTER 8 SHALL BE APPLICABLE |
| | THROUGHOUT THE BUILDING FOR THE NEW OCCUPANCY |
| | CLASSIFICATION BASED ON THE SEPARATION CONDITIONS SET |
| | FORTH IN SECTIONS 912.1.1.1 AND 912.1.1.2. |
| | |
| | 3) SHEET A1.02 INDICATES THE CENTRAL STAIR IS NOT A |
| | REQUIRED EGRESS STAIR PLEASE SHOW COMPLIANCE WITH: 2010 |
| | EXST BLDG CODE 912.4.1 MEANS OF EGRESS FOR CHANGE TO |
| | HIGHER HAZARD CATEGORY. |
| | WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A |
| | HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE |
| | 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| | CODE, BUILDING. PROVIDE MEANS OF EGRESS TO THE PUBLIC |
| | WAY FOR STAIR 2 & 3 FOR CHANGE OF USE TO A HIGHER |
| | HAZARD CLASSIFICATION. |
| | |
| | 4) PLEASE DESIGNATE WALL TYPE FOR THE SECOND FLOOR |
| | CORRIDOR, SEE 2010 FBC-B TABLE 1018.1 FOOTNOTE "C" |
| | CORRIDOR WALLS ARE TO BE SMOKE PARTITIONS IN ACCORDANCE |
| | WITH THE FIRE PREVENTION CODE. |
| | |
| | 5) PLEASE REVIEW DOOR HARDWARE REQUIREMENTS FOR THE NEW |
| | EDUCATIONAL OCCUPANCY UNDER 2010 FBC-B 1008.1.10 PANIC |
| | HARDWARE REQUIREMENTS FOR OCCUPANT LOADS OF 50 OR MORE |
| | IN (E) OCCUPANCIES. |
| | |
| | JAMES A. WITMER CBO |