| Date |
Text |
| 2013-07-22 14:16:32 | BUILDING PLAN REVIEW |
| | PERMIT: 13060770 |
| | ADD: LAMBERTON |
| | CONT: TBD (TO BE DETERMINED) |
| | TEL: (561)###-#### |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: JULY 22/2013 |
| | ACTION: DENIED |
| | FITNESS CENTER & MAIL KIOSK |
| | |
| | 1) MISSING SOILS REPORT. 2010 FBC-B 1803.6. |
| | |
| | 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) WALL LOUVERS, , |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | |
| | 4) SHEET A0.06 THIS IS A MIXED USE BLDG, A-3 GYMNASIUM |
| | 4A) REVISE COMMON PATH OF TRAVEL A3 <50 0CCUPANTS 75 FT |
| | FBC-B 1014.3 |
| | 4B) SINGLE EXIT FOR A3 <50 OCCUPANTS FBC-B T1021.2 |
| | 4C) OCCUPANCY MIXED USE A3/B |
| | 4D) A0.06 NOR A1.61 PLANS INDICATE OCCUPANT LOAD OF 31 |
| | USING 50 SQ FT WITH EQUIPMENT, EQUIPMENT NOT SHOWN. |
| | GYMS WITHOUT EQUIPMENT SHOWN 1/ 15 |
| | WHICH WILL INCREASE THE OCCUPANT LOAD TO 104 REQUIRING |
| | 2 DOORS. |
| | |
| | 5) A0.10 BUILDINGS ON THE SAME LOT, PLEASE PROVIDE AN |
| | ASSUMDED PROPERTY LINE BETWEEN TTHE FITNESS CENTER AND |
| | BUILDINGS 3 & 13, PROVIDE THE DISTANCE TO THE ASSUMED |
| | PROPERTY LINE FOR COMPLIANCE WITH 2010 FBC-B TABLE 602 |
| | & TABLE 705.8. |
| | |
| | 6) MISSING ON PLANS 2010 FBC-B 1209.2 ATTIC SPACES. |
| | AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM |
| | BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A |
| | CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762 |
| | MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE |
| | PROVIDED AT OR ABOVE THE ACCESS OPENING. |
| | |
| | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |