| Plan Review Notes For Permit 13060708 |
| Permit Number |
13060708 |
|
| Review Stop |
FIRE |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2013-09-13 10:46:05 | CLASS "B" MERCANTILE: NEED EMERGENCY LIGHTING. | | | EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM | | | OF 1.5 HOURS IN THE EVENT OF FAILURE OF NORMAL | | | LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE | | | ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT | | | LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, | | | NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF | | | EGRESS AT FLOOR LEVEL. |
|