| 2013-08-22 10:28:47 | PLUMBING PLAN REVIEW |
| | PERMIT: 13060708 |
| | ADD: 431 BUNKER RD |
| | CONT: GRUBER HALL CORP |
| | TEL: (561)697-3401 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE:8/22/13 |
| | ACTION: DENIED |
| | |
| | NOTICE: 2/22/13 TODAY I CALLED THE CONTRACTOR TO REACH |
| | OUT TO HIM, A MEETING WITH THE OWNER, CONTRACTOR, FIRE |
| | DEPARTMENT & THE BUILDING DEPARTMENT IS GOING TO BE |
| | REQUIRED. THE FIRE DEPARTMENT VISITED THE SITE, A FIRE |
| | INSPECTOR AND REQUESTED A 2 HOUR WALL BE INSTALLED |
| | BECAUSE OF THE TYPE OF USAGE FOR THIS SPACE. SINCE THEN |
| | THE PLANS HAVE INDICATED THE BACK HALF AS STORAGE AND |
| | NOW IT IS TO BE RETAIL WITH A 2 HR FIRE RATED WALL, |
| | INDICATING EXISTING RETAIL. THIS REVIEW WILL BE FOR A |
| | MERCANTILE OCCUPANCY. |
| | |
| | 1) ISSUES SSTAND WITH THE PLUMBING DRAWINGS, THE |
| | PLUMBING CONTRACTOR HAS NOT TAKEN RESPONSIBILITY FOR |
| | THE PLUMBING CONTRACTOR FOR THE PLUMBING SHEETS, THEY |
| | WILL NEED TO PRINT & SIGN THEIR NAME AND PROVIDE THEIR |
| | LICENSE NUMBER ON THE PLANS THEY HAVE DESIGNED. WEST |
| | PALM BEACH AMENDMENT TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION, 2010 EDITION 107.1. |
| | |
| | 2) AS IN THE BUILDING REVIEW, THE PLANS DO NOT INDICATE |
| | IF THIS IS GOING TO BE A SINGLE TENANT OR IF THIS WILL |
| | BE TWO TENANTS, WORST CASE A SINGLE MERCANTILE |
| | OCCUPANCY, SINGLE TENANT, 5000 SQ FT/ 30 SQ/ OCC EQUALS |
| | 167 OCCUPANTS. THE 2010 FBC-P TABLE 403.1(6) WILL |
| | REQUIRE ONE RESTROOM FOR BOTH MEN AND WOMEN. PLEASE NOT |
| | SINCE THERE IS A SHOWER, ONE WOULD HAVE TO BE PROVIDED |
| | FOR EACH SEX. |
| | |
| | THE SINGLE UNISEX RESTROOM WAS FOR ONLY FOR MERCANTILE |
| | OCCUPANCIES UNDER 3,000 SQ FT. IF THIS IS TO BE |
| | CONSIDERED TWO MERCANTILE OCCUPANCIES EACH 2,500 SQ FT |
| | THEN EACH TENANT SPACE WILL REQUIRE A UNISEX RESTROOM. |
| | NOTE THE TENANT SPACE NOT REQUIRING A SHOWER IN IT WILL |
| | ONLY NEED THE SINGLE UNISEX RESTROOM. |
| | |
| | 3) PLEASE ALSO REVIEW THE 2010 FBC-P TABLE 403.1(6) |
| | WILL REQUIRE A DRINKING FOUNTAIN PLEASE REVIEW 2010 FL |
| | ACCESSIBILITY CODE 211, |
| | 211.2 MINIMUM NUMBER. |
| | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | |
| | 4) THE RESTROOMS DESIGN ACCESSIBLITY NOR THE DRAINAGE |
| | AND VENT SYSTEMS WILL BE REVIEWED UNDER THIS REVIEW |
| | SINCE THEY WILL BE DRASTICALLY REVISED. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |