| 2013-07-29 11:10:22 | FBC 2010 EXISTING BUILDING CODE | | | FBC 2010 ACCESSIBILITY CODE | | | FBC 2010 PLUMBING REVIEW #2 | | | DENIED: | | | | | | 1. SHEET A-1 & P-1 ACCESS FOR THE PUBLIC TO THE | | | RESTROOM IS SHOWN THROUGH THE STORAGE AREA. | | | FBC PLUMBING 403.3.1 ACCESS. | | | THE ROUTE TO THE PUBLIC TOILET FACILITIES REQUIRED BY | | | SECTION 403.3 SHALL NOT PASS THROUGH KITCHENS, STORAGE | | | ROOMS OR CLOSETS. ACCESS TO THE REQUIRED FACILITIES | | | SHALL BE FROM WITHIN THE BUILDING OR FROM THE EXTERIOR | | | OF THE BUILDING. ALL ROUTES SHALL COMPLY WITH THE | | | ACCESSIBILITY REQUIREMENTS OF THE FLORIDA BUILDING | | | CODE, ACCESSIBILITY. THE PUBLIC SHALL HAVE ACCESS TO | | | THE REQUIRED TOILET FACILITIES AT ALL TIMES THAT THE | | | BUILDING IS OCCUPIED. | | | | | | 2. SHEET P-2 WATER FOR THE SHOWER IS SHOWN AS COLD | | | WATER ONLY. | | | FBC PLUMBING 607.1 WHERE REQUIRED. | | | IN OCCUPIED STRUCTURES, HOT WATER SHALL BE SUPPLIED TO | | | ALL PLUMBING FIXTURES AND EQUIPMENT UTILIZED FOR | | | BATHING, WASHING, CULINARY PURPOSES, CLEANSING, LAUNDRY | | | OR BUILDING MAINTENANCE. | | | | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|