2013-07-29 11:10:22FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #2
 DENIED:
  
 1. SHEET A-1 & P-1 ACCESS FOR THE PUBLIC TO THE
 RESTROOM IS SHOWN THROUGH THE STORAGE AREA.
 FBC PLUMBING 403.3.1 ACCESS.
 THE ROUTE TO THE PUBLIC TOILET FACILITIES REQUIRED BY
 SECTION 403.3 SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS OR CLOSETS. ACCESS TO THE REQUIRED FACILITIES
 SHALL BE FROM WITHIN THE BUILDING OR FROM THE EXTERIOR
 OF THE BUILDING. ALL ROUTES SHALL COMPLY WITH THE
 ACCESSIBILITY REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY. THE PUBLIC SHALL HAVE ACCESS TO
 THE REQUIRED TOILET FACILITIES AT ALL TIMES THAT THE
 BUILDING IS OCCUPIED.
  
 2. SHEET P-2 WATER FOR THE SHOWER IS SHOWN AS COLD
 WATER ONLY.
 FBC PLUMBING 607.1 WHERE REQUIRED.
 IN OCCUPIED STRUCTURES, HOT WATER SHALL BE SUPPLIED TO
 ALL PLUMBING FIXTURES AND EQUIPMENT UTILIZED FOR
 BATHING, WASHING, CULINARY PURPOSES, CLEANSING, LAUNDRY
 OR BUILDING MAINTENANCE.
  
  