2013-07-03 09:27:57431 BUNKER ROAD
 PERMIT #13060708
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLAN INDICATES ONE TENANT HAS TO ACCESS THE
 ADJACENT TENANT SPACE IN ORDER TO EXIT THE BUILDING.
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL EXIT DOORS,
 OCCUPANCY TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT
 SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON
 PATH OF TRAVEL ETC.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 90-MINUTE FIRE RATED DOORS ARE REQUIRED IN THE 2-HOUR
 FIRE RATED WALL AND DOORS SHALL BE POSITIVE LATCHING.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  