| Plan Review Notes For Permit 13060687 |
| Permit Number |
13060687 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-06-27 09:14:14 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. SUBSTRATE NOTED AS FILLED BLOCK. FILLED CELLS MUST | | | USE THE CONCRETE BLOCK SUBSTRATE ANCHOR SPACING, NOT | | | CONCRETE. | | | | | | 2. SEE SHEET 14, A 2" EDGE DISTANCE TO USE A FACTOR OF | | | .35 APPLIED TO ANCHOR SPACING. | | | | | | |
|