| 2013-08-02 18:01:08 | REVISION SECOND BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- REVISE ENERGY CALCULATIONS. NEED TO SPECIFY R-30 |
| | INSULATION IN THE CEILING AS REQUIRED BY TABLE 402A OF |
| | ENERGY CALCULATIONS SUBMITTED. |
| | |
| | 2- TYPICAL WALL SECTION ON SHEET A-4: |
| | A) R-30 CEILING INSULATION REQUIRED BY TABLE 402A OF |
| | THE ENERGY CALCULATIONS SUBMITTED DOESN'T FIT ON 2X8 |
| | WOOD JOISTS. REVISE AS REQUIRED. |
| | |
| | B) ORIGINAL COMMENT: "SPECIFY SIZE OF VENTILATION TO |
| | COMPLY WITH SEC. R806 OF 2010 FBC-RESIDENTIAL. ***NOTE: |
| | KEEP IN MIND THAT NEED CROSS VENTILATION". |
| | |
| | ***THIS COMMENT WAS NOT PROPERLY ADDRESSED. WALL |
| | SECTION SPECIFIES 4" X 6" VENT TO MATCH EXISTING. THIS |
| | DOESN'T PROVIDE CROSS VENTILATION AND VENT SPACING IS |
| | NOT SPECIFIED EITHER. REVISE AS REQUIRED. |
| | |
| | 3- MASTER BEDROOM EGRESS WINDOW: FLOOR PLAN ON SHEET |
| | A-2 SPECIFIES 52" X 60" SINGLE HUNG WINDOW, WHILE EAST |
| | ELEVATION ON SHEET A-3 SPECIFIES 52"X 54" SINGLE HUNG |
| | WINDOW. THERE IS A DISCREPANCY ON SIZE. REVISE AS |
| | REQUIRED TO MATCH AND MAKE SURE WINDOW COMPLIES WITH |
| | EGRESS SEC. R310. |
| | |
| | 4- ENGINEER TO USE CURRENT SEAL AS REQUIRED BY CHAPTER |
| | 471 FLORIDA STATUTE. SEAL USED SAYS "CERTIFICATE". THIS |
| | SEAL IS NO ALLOWED SINCE JANUARY 2006. NEED TO RE-SEAL |
| | ALL DRAWINGS AND THE RAS 117 CALCULATIONS SUBMITTED. |
| | |
| | 5- REVISION FEES WERE ADJUSTED ACCORDING TO EACH NEW |
| | SHEET SUBMITTED. OWES $339.00. THIS INCLUDES THE $30.OO |
| | ADDED BY ZONING FOR THEIR REVIEW. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |