| 2013-07-09 16:21:15 | RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- REVISE ENERGY CALCULATIONS SUBMITTED: ITEM # 7(B). |
| | NEED R-13 MIN TO COMPLY WITH TABLE 402A ON ENERGY |
| | CALCULATIONS SUBMITTED. |
| | |
| | 2- SHEET A-3B: |
| | A) SPECIFY INSULATION ON THE RAISED FLOOR. COORDINATE |
| | WITH ENERGY CALCULATIONS ITEM #1 ABOVE. SEC. 103.2.2 OF |
| | 2010 FBC-ENERGY CONSERVATION. |
| | |
| | B) TYPICAL WALL SECTION: |
| | (1) IT'S NOT CLEAR IF EXTERIOR WALL IS 2X4 OR 2X6. WALL |
| | SECTION CALLS FOR 2X4 DOUBLE TOP PLATE AND 2X4 BOTTOM |
| | PLATE, WHILE SPECS FOR WALL CALLS FOR 2X6 WOOD STUDS |
| | @16"O.C. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | (2) R-19 INSULATION SPECIFIED ON THE ENERGY |
| | CALCULATIONS DOESN'T FIT ON A 2X6 WALL. REVISE AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | (3) R-30 CEILING INSULATION REQUIRED BY THE ENERGY |
| | CALCULATIONS DOESN'T FIT ON 2X6 WOOD JOISTS. REVISE AS |
| | REQUIRED. ***NOTE; COORDINATE WITH ITEM #2 (B)(5) |
| | BELOW. SEC. 107.2.1 CITY AMENDMENTS. |
| | (4) ROOF SHEATHING SIZE SPECIFIED DOESN'T MATCH ROOF |
| | SHEATHING SPECIFIED ON THE DIAPHRAGM SCHEDULE ON SAME |
| | SHEET. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | (5) SPECIFY SIZE OF VENTILATION TO COMPLY WITH SEC. |
| | R806 OF 2010 FBC-RESIDENTIAL. ***NOTE: KEEP IN MIND |
| | THAT NEED CROSS VENTILATION. |
| | (6) PROVIDE COMPLETE SPECIFICATIONS FOR WOOD PROTECTION |
| | (FLOOR JOISTS) AS REQUIRED BY SEC. R317.1. |
| | (7) SPECIFY 7/8" MIN. STUCCO THICKNESS AS REQUIRED BY |
| | TABLE R702.1(1). |
| | (8) SPECIFY TWO LAYERS OF APPROVED WATER RESISTANT |
| | BARRIER AS REQUIRED BY SEC. R703.6.3. |
| | |
| | C) SPECIFY DIMENSION "A" ON ROOF ZONES SKETCH SHOWN |
| | ABOVE THE DIAPHRAGM SCHEDULE. SEE NOTE "A" ON FIGURE |
| | R301.2(7) AND ROOF SHEATHING NAILING ZONES FIGURE |
| | R803.2.3.1. |
| | |
| | D) ROOF PLAN: SPECIFY MIN. ROOF PITCH OF 1/4 PER FT. AS |
| | REQUIRED BY SEC. R905.11.1. |
| | |
| | 3- MASTER BEDROOM EGRESS WAS REDUCED WHEN CLOSING THE |
| | WINDOW TO ALLOW FOR THE BATHROOM ADDITION. NEED TO |
| | PROVIDE COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. |
| | R310. |
| | |
| | 4- LOW SLOPE ROOF: PROVIDE SIGNED AND SEALED RAS 117 |
| | CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER |
| | AREAS AS REQUIRED BY GENERAL LIMITATION #7 TO MEET THE |
| | DESIGN PRESSURES OF SEC. R301.2.1.4.3. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |